SLA Battery Cold Performance Tests: Gel vs. AGM

SLA Battery Cold Performance Tests: Gel vs. AGM

UNAVCO performed cold chamber tests to evaluate possible differences in cold performance between Gel and AGM, the two major types of Sealed Lead-Acid (SLA) batteries. Two tests were performed with one new Deka Gel Battery (P/N 8G31) and one new Deka AGM Battery (P/N 8A31). These tests also provide a benchmark against which to evaluate other battery types.

Test #1: Charge/discharge capacity at cold temperatures.

The batteries underwent identical charge/discharge tests at varying temperatures; no temperature compensation was applied to the charge routine. Each battery was allowed to equilibrate at the test temperature before two-stage charging. The "fast charge" stage brought the battery to 14.40 volts (2.40 volts/cell, 6 cells per 12 volt battery) with current limited to 1.5 amps. The "float charge" stage then held the battery at 13.80 volts for a maximum of 12 hours, with current limited to 1.0 amps.

Discharge capacity (in amp-hours) was then measured by applying a 1.0 amp load until 10.8 volts was reached. Note that the 1.0 amp discharge current is a significantly higher load than each battery would see in a field installation, where for example a 10-battery bank would power a 5 watt load. Time constraints did not permit testing with such extremely small discharge currents.

Results from the test series are presented in the table below. Since each battery had a different nominal capacity (8G31: 98 amp-hour, 8A31: 105 amp-hour), discharge capacities are provided in percent of their values at 25C.

Temperature (C) Pre-Test Soak
Time (hours)
GEL Capacity AGM Capacity
25 n/a 100% 100%
-20 24 24% 23%
-30 12 10% 13%
-35 12 3% 4%
-40 12 1% 2%
-45 12 0% 1%
-50 12 0% 0%
25 48 108% 96%

 

These results do not show a significant difference in the cold performance between Gel and AGM batteries in cold temperatures. Also, both batteries recovered fully after the test series.

The results also demonstrate the dramatic roll-off in capacity that lead-acid batteries typically experience in the cold. However it should be noted that because no temperature compensation was applied during the charge routine, the discharge capacities at low temperature are lower than results from manufacturer tests (where charging voltage is increased as temperature decreases).

Test #2: Recovery After Cold Exposure

To identify possible permanent damage as a result of extreme cold exposure, each battery was tested at room temperature after exposure to -70C. This temperature was chosen since a system on the Antarctic Plateau which turns off during the winter will quickly assume ambient temperature, but must still be chargeable when summer returns. The test was repeated with each battery in both the fully-charged and fully-discharged states.

Test Description GEL Capacity AGM Capacity
Soak fully-charged battery at -70C for 48 hours;
test after 48 hour soak at 25C
101% 92%
Soak dicharged battery at -70C for 48 hours;
test after 48 hour soak at 25C
97% 88%

 

This result indicates that the Gel cell may be more resistant to extreme cold than the AGM, however a much larger sample size would be necessary for validation. Overall, neither battery experienced a large, permanent drop in capacity from exposure to -70C, whether fully charged or discharged.

Attached Files
There are no attachments for this article.
Comments (3)
Comment by Angleterre on Wed, Dec 17th, 2014 at 1:48 AM
ults! Along with Liu Qinghe, after that mentally. Because of appease those who was simply just like a fire has been i just. <a href="http://www.knoqk.com/clubs-x-29.html" title="Angleterre">Angleterre</a>
Comment by john moore on Sun, Dec 2nd, 2012 at 5:14 PM
We inquiry any of this unit that is available in stock, Sealed Lead Acid Battery,AGM Battery,Dry cell battery and Heavy Duty battery Regards
Comment by gel battery on Wed, Aug 3rd, 2011 at 6:18 AM
Gel battery adopts gel electrolyte whcih allows you to mount the battery in any direction, even upside down, giving more flexibility to installers. Charging the gel battery needs to attach the red cable to "+", black cable to "-". Don’t mix it or it may damage the gel battery. Thank you for sharing this useful information with us. More information from Leoch International, http://www.leoch.com
Name
Email
Security Code Security Code
Related Articles RSS Feed
TLS - Acquisition of a Terrestrial Laser Scanning System for Polar Research (proposal, 25 January 2007)
Viewed 2676 times since Fri, Jan 31, 2014
Trimble NetRS - Power Draw Tests
Viewed 4528 times since Sun, Mar 28, 2010
Power - Wind Power Testing at UNAVCO through 2005, Phase 3
Viewed 3541 times since Sat, Mar 27, 2010
Power - Deep-cycle Batteries
Viewed 3120 times since Sun, Mar 28, 2010
Power Draw Profile for Trimble NetRS and Iridium Systems
Viewed 5696 times since Sat, Aug 28, 2010
Equipment Power Usage Testing
Viewed 8761 times since Sun, Mar 28, 2010
Septentrio PolaRx4 Power Consumption
Viewed 3546 times since Thu, Sep 29, 2011
Remote Station Power Analysis (2007)
Viewed 3147 times since Sun, Mar 28, 2010
Polar Station NetRS Receiver and Iridium Modem Configuration
Viewed 4591 times since Tue, Oct 27, 2009
Communications systems for remote Polar GNSS station operation (paper, 2007)
Viewed 1893 times since Thu, Feb 19, 2009
MENU

Last modified: Monday, 12-May-2014 00:18:29 UTC